The Setra Model 206 air transducer offers high performance, dependability, and versatility at a low cost. Designed for industrial and OEM use. It offers exceptional ±0.13% FS accuracy for pressure ranges as low as 25 PSI up to 10,000 PSI to meet a multitude of demanding applications.

The rugged stainless steel structure of the Model 206 withstands the rigors of the most difficult industrial applications. The unit meets NEMA 4 and IP65 environmental ratings, preventing unwanted moisture ingress.

Features

  • User accessible zero/span
  • Exceptional EMI/RFI
  • Absolute pressure option
  • Long-term stability: <0.5%/year
  • Reverse wire protection
  • Calibration NIST traceable
  • Wide operating voltage 12 VDC to 28 VDC
  • CE & RoHS compliant

Specifications

Performance Data

Accuracy RSS1 (at constant temperature)

±0.13% FS

Non-linearity, (BFSL) 25 PSIG range2

±0.1% FS / ±0.2% FS

Hysteresis

±0.08% FS

Non-repeatability

±0.02% FS

Response time

5 milliseconds

Long term stability

0.5% FS/YR

Thermal Effects

Compensated range

-4 to +176°F (-20 to +80ºC)

Zero shift

±1% FS/100°F (±0.9% FS/50ºC)

Span shift

±1.5% FS/100°F (±1.4% FS/50ºC)

Electrical Data (Voltage)

Excitation/ output

12 to 28 VDC reverse excitation protected

Power consumption

<0.15 watts (approx. 5mA @24VDC)

Output impedance

100 ohms

Circuit

3-wire (exc, out, com)

Vibration

200g operating

Environmental Data

Operating temperature

-40 to 185°F (-40 to +85°C)

Storage temperature

-40 to +185°F (-40 to +85°C)

Acceleration

10g Maximum

Shock

200g operating

Vibration

20g 50-2000 Hz

Electrical Data (Current)

Circuit

2-wire

Output

4 to 20 mA

Min. supply voltage (VDC)

9 + 0.02 x (resistance of receiver plus line)

Max. supply voltage (VDC)

30 + 0.004 x (resistance of receiver plus line)

Resources

You Might Also Like

All prices are in Australian Dollars and include GST. GST will be removed from your order if you are ordering from outside Australia.
Products may differ from pictured.
All trademarks and trade names are the properties of their respective owners. Wiltronics disclaims any proprietary interest in trademarks and trade names other than its own.

Setra Model 206 Air Transducer 206100-05

101-0060

$1672.00

We use cookies to ensure you have the best experience on our site. If you continue to use this site you consent to the use of these cookies. OK

Find out more in our Privacy Policy