Generator suitablility

  • 1.5kVA and larger, diesel or petrol generator
  • Frequency range 45 to 55Hz
  • Freqency to be stable
  • Voltage range 220 to 260VAC
  • Generator capacity through inverter limited to 4kW
Liquid Crystal Display (LCD)
The following signals can be viewed by scrolling the LCD: DC volts, DC charging amps, DC inverting amps, AC output volts, AC generator volts, AC generator frequency, generator power, inverter power, load power. Plus charge, boost and float voltage settings, and programmable parameters.

Applicable Standards
Designed and built to conform to:

  • AS3000 - SAA wiring rules
  • ISO 9001 - Quality Systems
  • AS2279 - Limitation of harmonics
  • AS1044 - Limits of electromagnetic interface
  • AS3100 - Requirements for Electronic Equipment
Battery charging parameters (user adjustable)
  Gel (sealed) Flooded
Charge Voltage


2.4 V/cell 2.5 V/cell
Float Voltage 2.33 V/cell 2.4 V/cell
Boost Voltage 2.45 V/cell 2.5 V/cell
Genset start (Low-voltage Alarm) contact closed on:
Battery 30% discharged (of size selected)
180% Load for 30 secs
150% Load for 2 minutes
120% Load for 10 minutes
100% Load for 30 minutes & battery < 2.1 V/cell

Brief Specifications
Nominal input voltage Vdc 24 48
Continuous rating(1) VA 1500 2000
60 minute rating(1) VA 1800 2500
12 sec surge rating(1) VA 3300 5500
Output voltage regulation(2) % <+/-1.5 <+/-1.5
Output frequency regulation(2) % <0.05 <0.05
Nominal output frequency Hz 50 50
Output waveform Sine Sine
Total harmonic distortion % <3.7 <3.7
Auto-start load(3) W 7-10 7-10
Auto-start power consumption(4) W 4 5.5
Low-load power loss(5) W 39 69
Efficiency 20-100% load: pf=1.0 % >85 >83
Efficiency 20-100% charging % >85 >83
Low volts shut-down (programmable) Vdc 22.2 44.4
High volts disconnect Vdc 36 73
Charge rating at nominal input volts A 0-60 60
Noise level (100% load) @ 1m approx db(A) 60 60
Nett weight approx kg 26.5 27
System continuous rating(6) VA 1500+G 2000+G
System surge rating(6) VA 3300+G 5500+G
Climate conditions

  • Ambient temperature 0 to 45 degrees C
  • Storage temperature -10 to 50 degrees C
  • Maximum relative humidity 95%
Colour
Case colour Magnolia (Cream)

Connections

  • AC Output connections Terminals
  • Generator connections Terminals
  • DC connections 1.5 meter long integal leads with crimped-on lugs.
Notes
(1) All ratings apply up to 25 degrees ambient temperature.
(2) For stand-alone operation
(3) Minimum load to automatically bring inverter into operation from search mode
(4) Power consumption while inverter is in search mode
(5) Power loss when inverted is in running at loads just above auto-start level.
(6) When generator connected: "G" = generator rating

Models

  • 1.5 INV024-240-1-IC000
    1.5kVA SUNSINE® Plus 24Vdc to 240Vac
  • 002 INV048-240-1-IC000
    2kVA SUNSINE® Plus 48Vdc to 240 Vac